供电电压 AC110-270V 输出电压24V。
故障显示 测试按钮 消音按钮 复位按钮
The ck1000 is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad. It also supervises all wiring, AC voltage and battery level.
This series of panels are basically the same in application and operation, their differences are shown in Table 1-1. HP101 will be described as the example in the following sections.
Table 1-1
FACP | Number of Detection Zones | Number of Sounder Outputs | Output Delay Settings |
CK1004 | 4 | 1 | N/A |
CK1008 | 8 | 2 | N/A |
CK1016 | 16 | 4 | N/A |
General
Conventional Fire Alarm Control Panel with four Zones
Key Specifications/Special Features
4/8/16 Style B (Class B) Initiating Device Circuits (IDCs).
All zones accept two-wire smoke detectors and any normally-open contact devices.
One built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
Alarm, Trouble and Supervisory, Form-C relays standard.
24-volt operation.
Resettable four-wire smoke detector power @ 500 mA.
Non-resettable power @ 500 mA.
One-man walk-test programmable for silent or audible test.
Disable/Enable control per IDC.
Reverse polarity protection.